dc.creator | Gamboa, Hugo Geovanni Gomes | |
dc.date.accessioned | 2018-07-19T13:31:13Z | |
dc.date.accessioned | 2023-03-22T17:30:23Z | |
dc.date.available | 2023-03-22T17:30:23Z | |
dc.date.issued | 2017-06-17 | |
dc.identifier.citation | GAMBOA, Hugo Geovanni Gomes. Influência de diferentes anticongelantes para a água gelada produzida por um chiller de absorção de LiBr em uma usina termoelétrica na absorção de gases. 2016. Dissertação (Mestrado) - Universidade Católica de Pernambuco. Programa de Pós-Graduação em Desenvolvimento de Processos Ambientais. Mestrado em Desenvolvimento de Processos Ambientais, 2016. | por |
dc.identifier.uri | https://hdl.handle.net/20.500.12032/76551 | |
dc.description.abstract | A lower specific fuel consumption has been the main reason for conducting research
and technological developments in thermal production area of energy. One of the
options to reach that desired condition is an efficient control of the engine block
temperature in the generator group of a thermal plant. To this, they were tested different
antifreeze, which gave the deionized water in preparation for the secondary refrigerant,
reductions in thermos physical properties of their specific heat and thermal conductivity.
After choosing the antifreeze with the help of experimental design using central
composite rotate design (CCRD), the 30 % ethylene glycol solution had their
performance compared to deionized water on a bench scale unit of a diesel generator
group. Experimental data on the response of aqueous solution of ethylene glycol,
against temperature variations at the entrance of the generator motor unit were
monitored and stored in an electronic register (FieldLogger) and subsequently analyzed
graphically with the aid of a computer. Although a lower value for the specific heat of
the aqueous ethylene glycol solution had, as expected, produced pulses faster
response to temperature changes in the engine block input, from the 70 ° C reduction
in thermal conductivity contributed to production of pulses lower for pure deionized
water. However, in the power range tested the aqueous solution of ethylene glycol
presented as advantages a reduction of specific fuel consumption of the order of 42%
between 68 °C and 75 °C. | eng |
dc.format | application/pdf | * |
dc.language | por | por |
dc.publisher | Universidade Católica de Pernambuco | por |
dc.rights | Acesso Aberto | por |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | |
dc.subject | Dissertations | eng |
dc.subject | Experimental planning | eng |
dc.subject | Antifreeze solutions | eng |
dc.subject | Rotational central composite design | eng |
dc.subject | Dissertações | por |
dc.subject | Planejamento experimental | por |
dc.subject | Soluções anticongelantes | por |
dc.subject | Delineamento composto central rotacional | por |
dc.title | Influência de diferentes anticongelantes para a água gelada produzida por um chiller de absorção de LiBr em uma usina termoelétrica na absorção de gases. | por |
dc.type | Dissertação | por |